Amana PTAC (PTH) - Cooling/Heat Pump/Backup Electric Heat - 7,000-15,000 BTU/h

Amana
SKU:
PTH073J35AXXX
Availability:
0-8 Week Lead Time
(No reviews yet)
Current Stock:
$917.99
Adding to cart… The item has been added

Specifications & Details

 

How to Identify Amana Nomenclature:

How to Identify Amana Power Cord Configurations:

Power Cord to Electric Heater Size Conversion:

208/230 Volt (250V Power Cords)

15 Amp - 1.5 kW & 2.5 kW

20 Amp - 3.5 kW

30 Amp - 5.0 kW

265 Volt (277V Power Cords)

20 Amp - 1.5 kW & 2.5 kW & 3.5 kW

30 Amp - 5.0 kW

Unit Product Data:

COOLING R32 Models
Model 1,7,9,10   PTH073J**AXXX PTH093J**AXXX PTH123J**AXXX PTH153J**AXXX PTH074J**AXXX PTH094J**AXXX PTH124J**AXXX PTH154J**AXXX
Voltage 1,3 230/208 230/208 230/208 230/208 265 265 265 265
Capacity (BTU/h) 7,100/7,000 9,000/9,000 12,000/11,600 14,600/14,400 7,300 9,000 12,000 14,600
Amps 11 3.2 4 5.6 7.1 2.8 3.5 4.9 6.6
Watts 11 570/545 725/720 1,040/1,005 1,400/1,355 585 725 1,060 1,405
EER 12.4/12.8 12.4/12.5 11.5/11.5 10.4/10.6 12.5 12.4 11.3 10.4
HEATING
Capacity (BTU/h) 6,300/6,100 8,200/8,000 11,000/10,800 14,300/14,000 6,500 8,200 11,500 14,100
Amps 11 3.2 4 5.6 7.1 2.8 3.5 4.9 6.6
Watts 11 510/480 665/650 980/955 1,350/1,320 545 685 1,020 1,375
COP 3.6/3.7 3.6/3.6 3.3/3.3 3.1/3.1 3.5 3.5 3.3 3
Unit without Electric Heater
Min. Circuit Amps 2,5,11 3.7 4.9 7.4 8.5 3.2 4.4 5.8 7.4
CFM (Cool/Wet Coil) High 330 290 330 400 330 290 330 400
Low 245 264 245 314 245 264 245 314
CFM (Dry) High 335 321 315 362 344 320 324 381
Low 307 292 293 348 344 320 324 381
Ventilated Air, CFM (Fan Only)** 65** 65** 65** 65** 65* 65** 65** 65**
Dehumidifaction (Pints/Hr.) 1.7 2 1.7 4.4 1.7 2 1.7 4.4
Net Weight (lbs.) 106 102 108 113 103 102 108 113
Ship Weight (lbs.) 115 117 125 130 115 117 125 130

 

COOLING R410A Models
Model 1,7,9,10   PTH073K**AXXX PTH093K**AXXX PTH123K**AXXX PTH153K**AXXX PTH074K**AXXX PTH094K**AXXX PTH124K**AXXX PTH154K**AXXX
Voltage 1,3 230/208 230/208 230/208 230/208 265 265 265 265
Capacity (BTU/h) 7,100/7,000 9,000/9,000 11,600/11,400 14,200/14,000 7,300 9,000 11,600 14,200
Amps 11 3.3 4.4 6.1 7.6 2.9 3.6 5.4 6.8
Watts 11 590/560 755/750 1,050/1,025 1,430/1,410 615 765 1,075 1,450
EER 12/12.4 11.9/12 11/11.1 9.9/9.9 11.9 11.8 10.8 9.8
HEATING
Capacity (BTU/h) 6,500/6,400 8,200/8,000 10,600/10,500 13,900/13,700 6,800 8,200 10,600 13,700
Amps 11 3.3 4.4 6.1 7.6 2.9 3.6 5.4 6.8
Watts 11 560/535 705/685 970/960 1,355/1,335 585 705 970 1,340
COP 3.4/3.5 3.4/3.4 3.2/3.2 3.0/3.0 3.4 3.4 3.2 3
Unit without Electric Heater
Min. Circuit Amps 2,5,11 3.7 4.9 7.4 8.5 3.2 4.4 5.8 7.4
CFM (Cool/Wet Coil) High 330 330 330 400 340 330 330 400
Low 245 264 245 314 245 264 245 314
CFM (Dry) High 317 298 303 376 340 318 342 390
Low 289 272 283 361 340 318 342 390
Ventilated Air, CFM (Fan Only)** 65** 65** 65** 65** 65* 65** 65** 65**
Dehumidifaction (Pints/Hr.) 1.7 2 1.7 4.4 1.7 2 1.7 4.4
Net Weight (lbs.) 106 102 108 113 103 102 108 113
Ship Weight (lbs.) 115 117 125 130 115 117 125 130

1. All 265-volt models must use an Amana brand sub-base (PTSB4**E) or an Amana brand hard-wire kit PTPWHWK4 and disconnect switch PSHW04A.

2. Minimum Circuit Ampacity (MCA) ratings conform to the National Electric Code; however, local codes should apply.

3. Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265-volt models is 239 volts; maximum is 292 volts.

4.Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models must be cartridge-style time-delay fuses (included and factory-installed on all Amana brand 265-volt chassis). See heater performance.

5.Heating capacity and efficiency based on unit operation without condensate pump.

 

6. Specify two-digit heater kW size to complete model number.

7. R-410A or R-32 refrigerant used in all systems.

8. All units meet or exceed ASHRAE 90.1 standards.

9. All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.

10. Refer to electric heat performance data for total MCA and recommended overcurrent protection. Amps and watts notation refers to compressor only.

11. All models, specification, decriptions, and data are not verified and subject to change. Verify information with manufacturer prior to purchase.

 

Manufacturers Standard Warranty: 1 Year Parts and Labor Full Unit 2-5 Years Parts 2-5 Years Part and Labor Sealed System * Confirm full warranty with manufacturer.